POWERHARD F RVFV-K & VVFV-K
LOW VOLTAGE
0,6/1kV
IEC 60502 - UNE 21123-2
Reference Norm


POWERHARD  F RVFV-K & VVFV-K

Protected power transmission.

Conductor: Electrolytic copper, class 5, based on EN 60228


Insulation: XLPE for RVFV-K or PVC for VVFV-K.
The standard identification is the following:
1 x natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey+ Blue (reduced cross section)
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Yellow/green + Blue


Armour bedding: PVC.


Armour: Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable.


Outer sheath: Flexible PVC outer sheath, black colour.


Applications: Due to its design, this cable is especially suitable for fixed installations that may be subject to mechanical aggression. It is highly recommended for use in installations in warehouses, production plants and agricultural facilities where the presence of rodents could imply a threat to cable integrity. At the same time, its use is recommended for street lighting installations.


National norm / european: EN 60332-1

International norm: IEC 60332-1


 

CHARACTERISTICS

Flexible conductor, class 5 Minimum service temperature: -15ºC Maximum service temperature: 90ºC/70ºC
 
Maximum short-circuit temperature: 250ºC (max 5 s) Minimum bending radius: 10 x cable diameter Meter by meter marking
 
Flame non-propagation Impact resistance: AG4. High impact Outdoor installation: permanent
 
Water resistance: AD7 immersion Chemical & oil resistance: good

INSTALLATION CONDITIONS

Industrial use Open air
 
Buried In conduit
 
Damp environment Rodent proof
 
Border