TOXFREE ZH RZ1-K (AS)
LOW VOLTAGE
0,6/1kV
IEC 60502 - UNE 21123-4
Reference Norm


TOXFREE ZH  RZ1-K (AS)

The halogen free power cable.

Conductor: Electrolytic copper, class 5 (flexible), based on EN 60228


Insulation: XLPE.
The standard identification is the following:
1 x Black
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross setcion)
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Yellow/green + Blue


Outer sheath: LSZH polyolephine outer sheath. Green colour, non-toxic and fire retardant.


Applications: The Toxfree RZ1-K (AS) cable with zero halogens is a high security cable. In case of fire, it does not emit toxic or corrosive gases, thereby protecting public health and avoiding any possible damage to electronic equipment. For this reason, its use is recommended in public places such as: hospitals, schools, museums, airports, bus terminals, shops in general, tunnels, the underground, etc., as well as in calculation centres, offices, production plants, laboratories, etc.


National norm / european: EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034

International norm: IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034


 

CHARACTERISTICS

Flexible conductor, class 5 Minimum service temperature: -15ºC Maximum service temperature: 90ºC
 
Maximum short-circuit temperature: 250ºC (max 5 s) Minimum bending radius: 5 x cable diameter Meter by meter marking
 
Flame non-propagation Fire non-propagation LSZH
 
Low smoke emission: Light transmittance > 60% Low corrosive gases emission Impact resistance: AG2. Medium impact
 
Outdoor installation: permanent Environmentally friendly Water resistance: AD3 Aspersion
 
Chemical & oil resistance: acceptable

INSTALLATION CONDITIONS

Public places Industrial use
 
Open air Buried
 
In conduit